TC Series DIN 72*72 Type                                               
 

 


TC-72 Series
TC72-AA-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Trimmer <Variable Resister>
Model:TC72-AA--
Alarm:
Non
Display Method:
Analog Deviation Meter
Display Tolerance:
1.0% of F.S.
Display Range:
±40°C
Setting Method:
Trimmer (Variable Resister)
Setting Tolerance:
1.0% of Setting Range
Setting Range:
0~100 , 0~200 , 0~400 , 0~600 , 0~1200
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-AA---A Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Trimmer <Variable Resister>
Model:TC72-AA---A
Alarm:
AL
Display Method:
Analog Deviation Meter
Display Tolerance:
1.0% of F.S.
Display Range:
±40°C
Setting Method:
Trimmer (Variable Resister)
Setting Tolerance:
1.0% of Setting Range
Setting Range:
0~100 , 0~200 , 0~400 , 0~600 , 0~1200
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-AD-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Trimmer <Variable Resister>
Model:TC72-AD--
Alarm:Non
Display Method:
14mm 7Segment Red LED
Display Tolerance:
0.5% of F.S.
Display Range:
0 ~ 999 or 0 ~ 1999
Setting Method:
Trimmer (Variable Resister)
Setting Tolerance:
1.0% of F.S.
Setting Range:
0 ~ 100 , 0 ~ 200 , 0 ~ 400 , 0 ~ 600 , 0 ~ 1200
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-AD---A Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Trimmer <Variable Resister>
Model:TC72-AD---A
Alarm:AL
Display Method:
14mm 7Segment Red LED
Display Tolerance:
0.5% of F.S.
Display Range:
0 ~ 999 or 0 ~ 1999
Setting Method:
Trimmer (Variable Resister)
Setting Tolerance:
1.0% of F.S.
Setting Range:
0 ~ 100 , 0 ~ 200 , 0 ~ 400 , 0 ~ 600 , 0 ~ 1200
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-AN-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Trimmer <Variable Resister>
Model:TC72-AN--
Alarm:
Non
Display Method:
Non
Display Tolerance:
Non
Display Range:
Non
Setting Method:
Trimmer (Variable Resister)
Setting Tolerance:
1.0% of Setting Range
Setting Range:
0~100 , 0~200 , 0~400 , 0~600 , 0~1200
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-DA-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC72-DA--
Alarm:
Non
Display Method:
Analog Deviation Meter
Display Tolerance:
1.0% of F.S.
Display Range:
±40°C
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999 , 0 ~1199
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-DA---A Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC72-DA---A
Alarm:AL
Display Method:
Analog Deviation Meter
Display Tolerance:
1.0% of F.S.
Display Range:
±40°C
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999 , 0 ~1199
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-DD-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC72-DD--
Alarm:
Non
Display Method:
14mm 7Segment Red LED
Display Tolerance:
0.5% of F.S.
Display Range:
-99 ~ 99 , 0 ~ 999 or 0 ~ 1999
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999 , 0 ~ 1199
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-DD---A Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC72-DD---A
Alarm:AL
Display Method:
14mm 7Segment Red LED
Display Tolerance:
0.5% of F.S.
Display Range:
-99 ~ 99 , 0 ~ 999 or 0 ~ 1999
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999 , 0 ~ 1199
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VAC
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm
TC-72 Series
TC72-DN-- Temperature Controller
HELP_FILE: NO FILE
Discription:Setting Method-Digital Switch
Model:TC72-DN--
Alarm:Non
Display Method:Non
Display Tolerance:Non
Display Range:Non
Setting Method:
Digital Switch
Setting Tolerance:
0.5% of Setting Range
Setting Range:
-99 ~ +99 , 0 ~ 199 , 0 ~ 399 , 0 ~ 599 , 0 ~ 999 , 0 ~1199
General Data
Sensor Type:
K(CA) , J(IC) or PT-100Ω
Output Method:
Relay(5A/250VAC) , Voltage(20mA/12V) , Linear(4~20mA)
Control Method:
P+D ON/OFF , ON/OFF or Proportion
Proportion Band:
Appro 2.5% of F.S
Cycle Time:
2 Sec or 20Sec (ON+OFF)
Manual Reset:
Trimmer: Range±10°C
Unit of Degree:
°C or °F
AL Alarm
Setting Method:
Trimmer(AL)
Setting Range:
0 ~ +50° , 0 ~ -50° or -50° ~ +50° of Setting Value
Output Method:
Relay , 0.5A/250VAC
HB Alarm
Setting Method:
Trimmer(HB)
Setting Range:
0.5A~25A ; 1.0A~50A
Output Method:
Relay , 0.5A/250VACphotogenic
Electrical Data
Power Supply:
110 / 220VAC ±20% 50/60Hz
Current Consumption:
2.5VA max.
Insulation Resistance:
Over 50MΩ/500VDC Between Power And Another Terminal
Dielectrical Strength:
Over 2.5KV /1min Between Power And Another Terminal
Mechanical Data
Operation Temp./Hum:
-20°C ~ +60°C ; 35%~85% RH
Vibration Resistance:
10 ~ 55Hz / 1.5mm , 2Hrs in X.Y.Z Direction
Panel Thickness:
1.0 ~ 8.0mm