Model |
TPS3-100
|
TPS3-125
|
TPS3-160
|
TSP3-200
|
Rated Current |
100A max.
|
125A max.
|
160A max.
|
200A max.
|
Protection Fuse |
100A.
|
125A.
|
160A.
|
200A.
|
Surge Current Duration |
1600A
|
2000A
|
2250A
|
5400A
|
Min. Block Voltage |
1600VAC
|
Cooling Fan |
120×120 / 230VAC
|
Main Power Supply |
180~440VAC 50/60Hz
|
Aux. Power Supply |
220VAC ±20% 50/60Hz
|
General Data
|
Leakage Current |
25mA max.
|
Surge Resistance |
Over 4KV
|
Noise Resistance |
±2KV / 1 μs
|
Input Method |
4~20mA/0~20mA/1~5V/2~10V/0~5V/0~10V or
VR-10K Ω selectable
|
Control Method |
Zero cross control
or phase angle control selectable ;
Excluding EPS2- □□□ & TPS2- □□□ |
Output Control |
Auto output or manual output selectable
|
Output range |
0~100%
|
Input resolution |
0.39%
|
Output low limit |
0~100% (L.000~L.100) settable
|
Output high limit |
0~199% (H.000~H.199)settable
|
Soft Start |
0~199 sec (t.00~t.199) settable
|
Dielectric Strength |
Over 2.5KV
|
Isolation Strength |
Over 100MΩ / 500VDC
|
Operating temp |
-20°C ~ +80 °C ; 35~85%RH
|
Housing Material |
Intensive PC+ABS (UL-94V0)
|